TM 5-3895-374-10
No.
Panel
Value
Operation
55
A
Feeder panel-select AUTO on the Divert switch (verify
that the Divert light continues to be illuminated).
56
A
Feeder panel-select AUTO on the four Feeder switches.
57
A
Feeder panel-press START on the Scalping Screen
button (the light will illuminate).
58
A
Feeder panel-press START on the Gathering Conveyor
button (the light will illuminate).
59
Keyboard
Keyboard-press ESCAPE, select targets (1), enter
starting feed rate-80 tons per hour, press ENTER.
60
Screen
Select desired mix formula (this must be pre-determined
and entered into the controller), ENTER.
61
A, B, D
Check all control panels to verify all motors are running
(no flashing lights).
62
Keyboard
Keyboard-press ESCAPE the feeders will start in
sequence.
63
A
Feeder panel-verify that the selected feeders are
running.
64
A
Feeder panel-check the feeder selector switch lights.
65
D
Burner control panel-when materiel begins to enter drum,
slowly increase burner firing rate by depressing the UP
ARROW on the Stack Control.
66
D
300 F
Burner control panel-increase until stack control reads
approximately 300°.
67
D
Burner control panel-maintain at this temperature by
increasing
(UP
ARROW)
or
decreasing
(DOWN
ARROW) the burner firing rate on the Stack Control.
page 2-106