TM 5-3895-374-10No.PanelValueOperation6MCC 1Turn ON main breakers on MCC 1 and MCC 2MCC 2NOTE110 Volt power should be available in the control house.7B460 voltsMotor control panel--verify on the motor control panel60 hertzthat the MCC 1 and MCC 2 voltage and frequency areindicating correct voltage and frequency.8AsphaltOn asphalt tanker panel for hot oil heater turn selectorTankerswitch to PUMP and verify pressure gauge on system is15 psi.9AsphaltCheck asphalt temperature gauge to see if heat isTankerrequired.10DBurner control panel-verify the Power selector switch isOFF.NOTEInside alarms at start up can be silenced on the feeder panel using the ALARMSILENCE push button (Panel A)11AFeeder panel-turn Powerkey ON-the outside warninghorn will sound after a brief delay.12DBurner control panel-turn Power selector switch to ON,and PRESS the AlarmSilencebutton to shut off thealarm.13DBurner control panel-select ExhaustShutterswitch toAUTO position.14A, B, DCheck panels for flashing lights (and alarm condition)and rectify this condition.15CASTCorner panel-check hot oil temperatures on the corner+25 Fpanel. These should read-inlet temperature within 25ofasphalt storage temperature. See step 9.page 2-101