TM 5-3895-374-10No.PanelValueOperation76 D +/-5 FBurner control panel-adjust materiel temperature, iftemperature is out of tolerance by more than 50, byadjusting the set point on the StackControl by thenumber of degrees that the materiel is in error.77D-.25 toBurner control panel-verify that the DamperControl is-.50 in.Control is maintaining a static pressure at the burner faceof approximately negative .25 to negative .50 inches.NOTEIf static pressure is out of tolerance select MANUAL by depressing Damper Manual/Auto switch(light will illuminate-to show manual position). (Panel D)78D-.25 toBurner control panel-to obtain a negative -.50 in.pressure of greater value open damper by PRESSINGthe Damper Open button to arrive at proper staticpressure. Opening the exhaust damper will decreaseback pressure. After the proper pressure is obtainedreturn Damperswitch to AUTO.79C< 6.0 inCorner panel-BaghouseDifferentialPressure monitorthis in conjunction with the DamperControl. Baghousedifferential pressure should not exceed approximately 6.0in. If it is above this value, bag efficiency has decreasedand needs to improve. Lower production rate to allowbaghouse to clean and become more efficient.Differential pressure may decrease after a period of time.80B60+/-1Motor control panel-monitor the frequency meters on aregular basis. They should read 60 hertz + or-1 (notrequired when on utility power).81BMotor control panel-surge bin loading. Alarm will soundand red light on SurgeBinHighLevel will flash when binis nearing capacity.page 2-108