TM 5-3895-374-24-2FIGURE CThe maximum length of connecting wire between thetransmitter and the receiver is a function of wire size andreceiver resistance. That portion of the total current loopresistance represented by the resistance of theconnecting wires themselves should not exceed .,j% ofthe receiver resistance. For extremely long runs (over1,000 feet), it is desirable to select receivers with higherresistances in order to keep the size and cost of theconnecting leads as low as possible. In installationswhere the connecting run is no more than 100 feet,connecting lead wire as small as No. 22 Ga. can beused.FIGURE DSeveral Series 604 transmitters can be operated with asingle power ply as depicted above in Figure D. Becareful to specify a supply with sufficient capacity. Theminimum current requirement at a given voltage can becalculated by multiplying the number of units x 20 mA. Inthe example shown this would be 4 x 20 or 80 mAminimum.PRESSURE RANGINGEach Series 604 Transmitter is factory calibrated to therange given in the model number chart. However,special calibration is also available. If this is the case,the transmitter will be so marked. For purposes ofclarification in these instructions, range is defined as thatpressure which applied to the transmitter produces 20milliamps of current in the loop. Zero pressure is alwaysassumed to be 4 milliamps.If a transmitter pressure range other than that supplied isrequired, the following re-ranging procedure should befollowed:1.With the transmitter connected to the companionreceiver per the instructions above, an accuratemilliammeter with a full scale reading ofapproximately 30 milliamps should be inserted inseries with the current Ioop. A controllablepressure source capable of achieving thedesired range should be connected to the highpressure port of the transmitter and teed into anaccurate reference pressure gage ormanometer. Be sure to vent the low pressureport to atmosphere. The instrument must beranged in the same position in which it will beused. Vertical mounting recommended.2.Apply electrical power to the system and allow itto stabilize for 10 minutes.3.With no pressure applied to transmitter, use"zero" adjustment to set loop current at 4 mA.4.Apply full range pressure and set loop current at20 mA using "span" adjustment.5.Relieve pressure and allow transmitter tostabilize for 2 minutes.6.Zero and span adjustments may be interactiveso repeat steps 3 through 5 until zero and fullrange pressures consistently produce loopcurrents of 4 and 20 mA respectively.7.Remove the milliammeter from the current loopand proceed with final installation of thetransmitter and receiver.(page 3-711)
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business