Configuration, special functions, settings
TM 5-3895-374-24-1
Summary
CONFIGURATION
INPUTS-OUTPUTS
SPECIAL FUNCTIONS
SETTINGS
Rated frequency
*50 Hz,
Assignment LI1
Freewheel stop
Linear N. quadratic P,
Fast stop
U/F Iaw
Linear N, quaratic P,
linear F, linear L
Acceleration
0.2 to 990 s
(5 s)
Deceleration
Current Input
0-20 mA, 4-20 mA, 20-4 mA
Reduce voltage
Reduce current limitation
Switch to ramp 2
Store reference
Rated motor voltage
Automatic. 220/240 V
380/415 V, 440/460/500 V,
525/575 V
0, 2 to 990 s
(10 s)
Low speed
0 to HSP(Q)
(Q)
Voltage / frequency
Coupling 1 (high), coupling 2 (low)
Local control
Remote PBU
Fault reset
Selection of motor 2
Motor thermal protection
Yes, no, moto-ventilated motor
High Speed
LSP to max frequency
(*50 Hz**60 Hz)
Maximum frequency
*67 , 87, 110 Hz
**80.4, 104, 120, 132 Hz
Preset speeds
+ speed
Assignment LI2
Freewheel stop
Frequency loop
Yes, no
Ramps
U/F adjustment
N/P/F/L from 00 to 99
(N00)
I thermal
Slip compensation
Yes, no
Fast stop
DC braking
Reduce voltage
Reduce current limitation
Linear S. Parabolic
Deceleration ramp adaptation
0,45 to 1,05 In
(0.9 In)
Stability
0 to 100
(0)
Preset speeds
No. 2, 4, 8
Store reference
Switch to ramp 2
Local control
Remote PBU
Yes, no, braking module
Skip frequencies
No, 2 Hz. 5 Hz
Slip compensation
0 to 5 Hz
(acc. to rating)
+speed / -speed
No, yes
Fault reset
Selection of motor 2
Preset speeds
- speed
DC stop
Yes, no
Low speed freewheel
Preset speeds 1 to 6
LSP to HSP
(LSP)
Reduce current limitation
Reduce voltage In FW direction
No, yes, logic input. remote
Asignment DCB
Freewheel stop
Fast stop
DC braking
No, yes
Catching a spinning load
150 % to 5 %
(150%)
Acceleration 2
0.2 to 990 s
(5 s)
Reduce voltage In RV direction
No, yes. logic input
Reduce voltage
Reduce current limitation
Switch to ramp 2
Store reference
No, yes
Automatic restart
DeceleratIon 2
0,2 to 990 s
(10 s)
Reduce current limitation
No, remote, local
Local control
Remote PBU
Fault reset
Selection of motor 2
Preset speeds
No, yes
Mains fault validation
Yes, no
TG feedback function
Freq loop Again
0 to t00
Skip frequency 1
0 to HSP
(*50 Hz, **60 Hz)
Acceleration torque
No, yes
*
ATV - 452 *** M
ATV - 452 ***
**
ATV - 452 *** N
ATV - 452 *** S
Analog outputs
0 - 20 mA, 4 - 20 mA
Assignment A01
Motor frequency
Motor current
Motor thermal state
Motor load
HSP attained
LSP attained
Reference attained
Current limitation
Motor thermal state > 100%
Regulation - Safety
Regulation
Safety
Skip frequency 2
0 to HSP
(*50 Hz, **60 Hz)
I thermal 2
0,2 to 1,05 In
(0.9 In)
DC braking level current
0,2 to 1,5 In
(0.5 In)
DC stop level current
0,5 to 21,5 In
(In)
The underlined values
are the factory settings.
Motor thermal state > 118%
Assignment A02
Motor frequency
Motor current
Motor thermal state
Motor load
HSP attained
LSP attained
Reference attained
Current limitation
DC stop time
0,5 to 4 s
(0.5 s)
Brake control threshold
0 to In
(0)
Brake release threshold
0 Hz to LSP
(0 Hz)
Motor thermal state > 100%
Motor thermal state > 118%
Brake engage threshold
0 Hz to LSP
(0 Hz)
Brake release time delay
0 to 4 s
(0)
(page 3-246)