TM 5-3895-374-24-1
Configuration, special functions, settings
Special functions
Functions
Selection
Factory setting
Description
DC stop
Yes / No
Yes
DC injection braking when the output frequency
becomes <1 Hz (otherwise, locking)
Current and duration adjustable (p 93)
Low speed freewheel
No / Yes
No
Validation of this function causes the speed
controller to lock should the frequency drop to
below the low speed value
Applications: tapered rotor motors
Catching a spinning load
No / Yes
No
This function avoids, in the event of a short
(see recommendations
mains failure (> 20 ms), a break in the motor
following page)
speed
Function off:
when restarted, the output frequency develops
from zero to the reference value
Function on:
when restarted, the output frequency is imme-
diately equal to the reference value, the voltage
develops progressively so as not to cause an
overcurrent
CAUTION:
when
operating,
this
function
requires a special control sequence maintaining
power and control supply, maintaining the speed
reference and the operating direction signal (FW
or RV) If one of these signals is only validated
after restoration of the voltage, speed returns to
the required value according to the ramp (reset to
zero) Motor brakes in order to pull into the ramp,
and there is a risk of 06F fault (excessive
braking)
Applications machines for which loss of speed
is slight during short mains failures
Automatic restart
No/ Yes
No
Activation of this function enables automatic
(see recommendations
restarting of the speed controller, following an
on following page)
excessive braking fault or a motor overload
fault.
In the event of locking, following excessive
braking, the speed controller remains locked for
1 minute with display of code 06F and restarts
automatically if the fault has disappeared. and
if the other operating conditions allow this
If overvoltage occurs again, the locking for
one minute and restart command sequence is
repeated 4 times (that is a maximum of 5
sequences) before the speed controller locks
permanently
In the event of locking, following motor over-
load, the speed controller remains locked for as
long as the thermal state stays higher than
100 % (about 7 minutes) Restarting is possible
if the other operating conditions allow this
For both these faults, the safety relay (contact
to terminals SA-SB) remains closed
Applications: machines or installations opera-
ting without supervision
(page 3-241)