TM 5-3895-374-24-1Configuration, special functions, settingsAssignments of the inputs/outputsThe A01 and A02 analogue outputs can be modified, and assigned according to the data in the following table belowValuesFactory settingDescriptionAnalogue outputs0-20 mA0-20 mAOutput signals A01 and A02 varying from 0 to4-20 mA20 mA or from 4 to 20 mA according to selectionAssignment ofMotorA01Analogue output A01 assigned to Motoroutput A01 or A02frequencyfrequency signalScale factor 20 mA = high speedMotorA02Analogue output A02 assigned to Motor currentcurrentsignalScale factor 20 mA = maximum speed control-ler transient current (p 10 and 11)MotorAnalogue output A01 or A02 assigned to Motorthermal statethermal state signalScale factor 20 mA = 150 %Motor loadAnalogue output A01 or A02 assigned to Motorload signalScale factor 20 mA = 200 %* HSP attainedAnalogue output A01 or A02 assigned to HSPattained logic functionLogic level 0:0 or 4 mALogic level 1:20 mA* LSP attainedAnalogue output A01 or A02 assigned to LSPattained logic function* Reference attainedAnalogue output A01 or A02 assigned toreference attained logic function* Current limitationAnalogue output A01 or A02 assigned to I limitlogic function* Motor thermal stateAnalogue output A01 or A02 assigned to Motor>100 %thermal state > 100 % logic function (thermalpre-alarm)* Motor thermal stateAnalogue output A01 or A02 assigned to Motor>118 %thermal state > 118 % logic function (thermalalarm)* Analogue output A01 or A02 assigned to a logic function use a reference LA4-DWB interface tocontrol an LC1 -D contractor or a CA2-DN control relay(page 3-238)