TM 5-3895-374-24-1
Configuration, special functions, settings
Assignments of the inputs/outputs
Possible assignment
Description
Local control
Concerns control of the speed controller by serial link (point to point or multidrop)
When the logic input assigned to this function iS validated, the speed controller is no
longer controlled by the serial link, but by its logic inputs (local control)
Remote PBU
Validation of the logic input assigned to this function has the same effect as pressing the
PBU push-button on the dialogue unit (see p 40 onwards)
* Prolonged pressing causes the scrolling of the parameters on the displays
* Short pressing recalls the parameter type
Fault reset
Validation of the logic input assigned to this function causes the stored fault to be erased
and the controller to be reset if the cause of the fault has disappeared
Erasable faults: 0SF , 0LF , 0LF , 0bF , 0bF , 0hF , SPF , SPF , SLF .
Note: faults PhF and USF are not stored
Other faults cannot be erased by this function, as they require monitoring of the
controller and of the installation
Selection of motor 2
Validation of the logic input assigned to this function allows configuration of a second
motor thermal protection value (0,2 to 1,05 in, preset 0,9 in) This alternative can only be
selected when the controller is locked DC braking level current, DC stop level current,
and brake control threshold are also adapted according to the ItH1 / ItH2 ratio (p 93)
Applications: * alternating multiaxis control of two types of motors with different power
ratings,
* operating two-speed motors with separate windings,
* controlling two different numbers of motors in parallel
(page 3-237)