TM 5-3895-374-24-232.Set and check operation of:A)Low and high gas pressure switches. See gaspressure switch manufacturer’s instructions fordetailed procedures. Units with mercuryswitching device must be properly leveled.(1)For initial start up:Once the burner’s normal operational gaspressure has been set, adjust the low andhigh gas pressure switches as follows:(a)Low gas pressure switch. With theburner running, slowly close the main gastrain manual shutoff cock and adjust theswitch to open its circuit when thepressure falls below its normal value.The burner will shut down. Open themanual gas shutoff cock to the full openposition and manually reset the Low GasPressure Switch. The burner will restart.(b)High gas pressure switch. With theburner running, adjust the switch to apoint where the switch opens its circuit.The burner will shut down. Manuallyreset the switch and readjust the cutoutpoint to be made at the normal operatingpressure, but to open if the pressure goesslightly above normal.B)All burner and heat exchanger controls andoperating devices.C)Blower Combustion Air Flow Switch(1)Shut burner power off.(2)Disconnect both wires at the air flowswitch and temporarily clip them together.Make sure that they cannot ground againstanything, since they will be powered with110 Volts during the test.(3)Put a continuity meter across the commonand normally open terminals on the airswitch.(4)Close the gas train checking cock.(5)Start the blower motor. The meter shouldread electrical continuity as soon as theblower starts.(6)Disconnect the blower motor lead wire orthe wire which energizes coil of motor re(starter), or open the main powerdisconnect switch to the burner. Within 4to 5 seconds after the blower motor is de-energized, the meter should indicate anopen air flow switch circuit (no continuity).(7)If the switch does not open in 4 to 5seconds, readjust accordingly. Turn theair flow switch adjustment screw clockwiseto shorten cut-off response time, andcounterclockwise to lengthen cut-offresponse time.(8)Turn the burner power off. Remove theshorting clip from the two disconnectedwires and let them hang loose. (They willbe powered with 110 Volts, so don’t letthem ground out.)(9)Open the gas train checking cock. Turnthe burner on. With the wiresdisconnected, the burner should go into apurge cycle, although neither the ignitionnor the main fuel valve circuits will beenergized. If they do energize, there is awiring problem. Correct as required.(10)Turn power off. Reconnect the air flowswitch wires to the air flow switchterminals. Place burner back into normaloperation.33.The “Owner's Operating Instructions,” page 43 ofthis manual, should be posted in a clearly visiblelocation close to the burner.34.If the burner operation is abnormal, refer toSection 7, “Trouble Shooting Suggestions,” aswell as trouble shooting information included inthe flame safeguard manufacturer's bulletinshipped with the burner. It is also stronglysuggested that all test procedures outlined in theflame safeguard control manufacturer's bulletin beconducted.35.Complete the “Burner Start Up Information andTest Data” sheets on pages 41 and 42.6. OIL START UPRefer to page 21, “General Start Up Procedure - All Fuels” and toSection 3 for mechanical operation detail of specific mode ofoperation. Combination Gas/Oilsystems should also refer to page 22, “Information on Fuel/AirModes of Operation for Combination Gas/Oil Units.”General InformationPower Flame Type C oil burners are of the pressure atomizingforced draft type, using a single simplex or bypass type nozzlesystem. On/Off burners use a simplex nozzle. Fixed air low firestart burners use a simplex nozzle with a bypass valve to allowreduced oil nozzle pressures at light off. Low/High/Off andLow/High/Low burners have movable air dampers and may use asingle simplex or bypass type oil nozzle with a bypass valve toallow reduced oil pressures at light off and at low fire. Modulatingburners have movable air dampers and use a single simplex orbypass type oil nozzle with a proportioning metering valve in thenozzle return line to allow modulated fuel inputs from low to highfire.Some applications may require the burner to function at the lowend of its rated capacity. As a result, the two combustion air inletsmay supply more air than is required for efficient combustion. Itmay therefore be desirable to operate the system using only onecombustion air inlet and one combustion air inlet damper. Thismay be accomplished by removing cross connecting linkagebetween dampers and locking the unused damper in a fixedposition.One way of locking the damper is to use a 10-24 machine screwthrough the hole in the linkage arm, and drill and tap the air inlethousing or use two nuts on the screw and let the screw bearagainst the air inlet housing. Air diffuser movement (fore and aft)may be necessary to produce the best flame pattern or smoothestoperation. See page 20, “Gas, Oil or Gas/Oil Burners DiffuserAdjustment,” for further information.Gas and Gas/Oil burners for Scotch marine and other selectedapplications incorporate a gas/air premix adjustment. Thisadjustment is identified by diametrically opposed adjustment knobson the blast tube. See page 20, “Gas or Gas/Oil Burner andFuel/Air Premix Adjustment” for further information.(page 3 - 978)
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business