TM 5-3895-374-24-1
Commissioning terminal
Fault display
In the event of the speed controller locking, the nature of the fault appears on the screen
However, the display of electrical quantities remains possible by pressing keys and
Faults which may appear
Speed
Explanations
on the screen
controller
code
Phase failure
PHF
Mains phase failure
Undervoltage
USF
Mains supply too low
Overvoltage
OSF
Mains supply too high
OverterPerat.
OhF
Speed controller overheated
Motor overload
OLF
Motor overload, thermal protection tripped
Motor Phase
OLF
Current loss in a motor phase
Overbraking U
ObF
Overbraking (overvoltage)
Overbraking 1
ObF
Overbraking (overcurrent)
Overcurrent 1
OcF
Transient overcurrent or short-circult
Overcurrent 2
OcF
Transient overcurrent or short-circuit
Cap. relay
CrF
Capacitor charge relay closure command
fault
Overspeed
SPF
Speed regulation fault, incorrect setting or
Tacho failure
SPF
No TG feedback signal
Serial link
SLF
Serial link communication fault
Intern
InF
Internal connection fault
Store fault
InF
EEPROM memory storage fault:
recall the factory settings (p. 110)
or the customer settings (p. 111)
Autotest inval
InF
Autotest invalid the AUTOTEST switch has
been moved to the ON position during speed
controller operation
(page 3-255)