TM 5-3895-374-24-1Commissioning terminalFault displayIn the event of the speed controller locking, the nature of the fault appears on the screenHowever, the display of electrical quantities remains possible by pressing keys andFaults which may appearSpeedExplanationson the screencontrollercodePhase failurePHFMains phase failureUndervoltageUSFMains supply too lowOvervoltageOSFMains supply too highOverterPerat.OhFSpeed controller overheatedMotor overloadOLFMotor overload, thermal protection trippedMotor PhaseOLFCurrent loss in a motor phaseOverbraking UObFOverbraking (overvoltage)Overbraking 1ObFOverbraking (overcurrent)Overcurrent 1OcFTransient overcurrent or short-circultOvercurrent 2OcFTransient overcurrent or short-circuitCap. relayCrFCapacitor charge relay closure commandfaultOverspeedSPFSpeed regulation fault, incorrect setting orTacho failureSPFNo TG feedback signalSerial linkSLFSerial link communication faultInternInFInternal connection faultStore faultInFEEPROM memory storage fault:recall the factory settings (p. 110)or the customer settings (p. 111)Autotest invalInFAutotest invalid the AUTOTEST switch hasbeen moved to the ON position during speedcontroller operation(page 3-255)