TM 5-3895-374-24-1
Chapter 9
Troubleshooting
The Following
Probable Cause
Recommended Action
Error Exists
1.
Verify selected processor mode
2.
If the processor is in the Program/Test modes,
attempt Run mode entry
If keyswitch is in the REM position and
Either Improper
there is no key, use the programmer
Mode Selected or
If keyswitch is in REM or PROG position,
User Program
and you have the key, toggle to the RUN
Logic
position
3.
If in the suspend mode, check user program logic
for suspend instructions
Refer to the Advanced Programming Software User
Manual (Catalog Number 1747-NM002)
1.
Check proper 120/240V power supply jumper
selection and Incoming power connections
Line Power Out of
2.
Monitor for proper line voltage at the incoming
Operating Range
power connections
See page 5-4 for power supply installation
Processor Not In
1.
Remove power and inspect the power supply
Run Mode
chassis connections and the processor chassis
Improper Seating
connections
of Power Supply,
and/or Processor
2.
Reinstall the devices and re-apply power
Important The processor only operates In slot
in the Chassis
0 of chassis #1
1.
Attempt Run mode selection of Processor in
existing chassis
keyswitch is In the REM position and
there is no key, use the programmer
keyswitch is in REM or PROG position,
and you have the key, toggle to the RUN
Defective
position.
Processor, Power
2.
Place processor in another chassis not in the
Supply, or Chassis
existing system. Apply power, reconfigure and
attempt Run mode selection. If unsuccessful,
replace processor.
3.
Try existing power supply in test chassis. If
unsuccessful, replace power supply. If entry into
the Run mode is allowed, replace the existing
chassis.
Refer to the following key to determine the status
of the LED indicators.
Indicates the LED Is OFF
Indicates the LED Is ON
Indicates the LED is FLASHING
Status of LED does not matter
(page 3-446)