TM 5-3895-374-24-1
Chapter 9
Troubleshooting
PROCESSOR ERRORS
Error
Code
Module Display
Fault Description
0034
BAD TIMER DATA
A negative value for a timer accumulator or preset value was
detected
0035
BAD INST IN INTR
TND, SVC or REF instruction is called within an interrupting or
user fault routine.
0036
BAD PID PARAM
An invalid value is being used for a PID instruction parameter
0038
RET IN FILE 2
A RET instruction was detected in a non-subroutine file.
xx39?
BAD STxx:LEN
Invalid string length in string file.
xx50
SLOT xx DATA ERR
A rack data error is detected at the slot specified
xx51
SLOT xx MOD ERROR
An I/O module runtime error at the slot specified.
xx52
SLOT xx MOD RMV
A module required for the user program is detected as
missing or removed at the slot specified.
xx53
MOD IN SLOT xx
At going-to-run, a user program declares a slot as unused,
and that slot is detected as having an I/O module inserted.
xx54
SLOT xx MISMATCH
A module required for the user program is detected as being
the wrong type.
xx55
SLOT xx MOD ERR
A module required for the user program is detected as having
the wrong I/O count or wrong I/O driver.
0056
SLOT 00 BAD CFG
The rack configuration specified In the user program is
incorrect.
xx57
SLOT xx COMM ERR
An intelligent I/O module has not responded to a Lock Shared
Memory command within the required limit.
xx58
SLOT xx SVO ERR
A specialty I/O module generated a generic fault.
xx59
SLOT xx SI/O ERR
An intelligent I/O module has not responded to a command as
being completed within the required time limit.
? Error codes for 5103 Processor only
page 3-406