TM 5-3895-374-10
1.
Batcher Fails To Open
The batcher gate on the surge bin when in the automatic mode (selected when in production) is time controlled by the PLC.
An "open" time and a "closed" time have been input (see Maintenance manual for additional information). The gate cycles
open and then closed continuously while the plant is producing. Failure of the gate to open when signaled could cause the
plant to shut down with hot mix in the components. This could result in damage to the equipment if the hot mix cools and
hardens.
No.
Panel
Operation
1
B
Motor control panel-set Batcher to the OPEN position.
2
Visual
Check
Verify batcher gate opens, if it fails to open, proceed as follows.
3
B
Motor control panel-press STOP button on Hot Mix Conveyor.
4
D
Burner control panel-select OFF on the Main Flame selector switch.
5
A
Feeder panel-verify that the Divert light switches from Drum to DIVERT.
6
B
Motor control panel-press STOP button on Exhaust Fan.
7
D
Burner control panel-press STOP button on Burner Fan.
NOTE
Correct the problem.
2.
Hot Mix Conveyor Fails
No.
Panel
Operation
NOTE
The following will stop: drum, feed conveyor, screen, gathering conveyor and feeders
page 2-121