TM 5-3895-374-10No.PanelOperationNOTEPerform a hot shut down (see section 2-16)NOTECorrect the problem.8.Baghouse Inlet Gas Temperature Exceeds 400°No.PanelOperation1DBurner control panel-select OFF on the MainFlameselector switch.2DBurner control panel-select CLOSED on the ExhaustShutter selector switch.3AFeeder panel-select DIVERT on the Divert selector switch.4BMotor control panel-press STOP button on ExhaustFan.5DBurner control panel-press STOP button on BurnerFan.6BMotor control panel-select OPEN on the DropOut selector switch.NOTEContinue to feed aggregate through the plant to lower the plant temperature monitored on the Stack Control(Panel D). At a temperature of 3250 proceed as follows:7KeyPress ESCAPE-targets (1), zero (0), ENTER, ESCAPE.NOTEContinue a normal plant shut down rejecting aggregate passing through the drum at the drop out gate in the hotmix conveyor.NOTECorrect the problem.page 2-124