INTERNAL LONG TIME DELAY SELECTION
RELAY SETTINGS

TM-5-3895-374-24-1 Paving Machine Bituminous Material: Crawler Mounted Diesel Engine Driven Manual
Page Navigation
  81    82    83    84    85  86  87    88    89    90    91  
TM 5-3895-374-24-1 FIGURE 5 Note: All Power Supply and Test Ckt. Connections Are Not Shown For Clarity.  See Fig.  2 For Complete Individual Relay Wiring TRIP COIL REQUIREMENTS A circuit breaker or switch used with the Type GC Ground Fault System must have a trip coil capable of operating reliably at 55% of rated voltage.  Inrush current must not exceed 50 amperes at rated voltage.  Sealed current must not exceed 10 amperes  unless  coil  clearing  contacts  (52a)  are  used.    Coil  clearing  contacts  are  required  for  trip  coils  not  rated  for continuous duty at 120 Vac. (page 3-94)