• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
SENSOR MOUNTING
INTERNAL LONG TIME DELAY SELECTION

TM-5-3895-374-24-1 Paving Machine Bituminous Material: Crawler Mounted Diesel Engine Driven Manual
Page Navigation
  79    80    81    82    83  84  85    86    87    88    89  
TM 5-3895-374-24-1 FIGURE 4 CONNECTIONS Connections for standard application should be made according to the wiring diagram In Figure 2 Wires from the Sensor to the Ground Fault Relay should be no longer than 25 feet and no smaller than No.  14 AWG.  Wires from Monitor Components should be no longer than 50 feet and no smaller than No 18 AWG Wires 1, 2 and 3 and Control Transformer should be sized to deliver the necessary current to the Trip Coil at 55% rated output voltage of the Control Transformer. When zone selective interlock wiring Is used, Ground Fault Relay interconnections should be no smaller than No.  18 and no longer than 100 feet These wires should be routed separately from any power wiring All wiring should be protected from arcing fault and physical damage by barriers, conduit, armor or location. When two wires are used under one terminal on the Sensor, both shall be No.  14. (page 3-92)







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.