TM 5-3895-374-24-2The flame amplifier module is installed in the secondset of guide channels found in the EB700 FLAME-MONITOR Chassis. It is marked "AMPLIFIERMODULE".Do not force the module into position.CAUTION: Remove power from the wiring basebefore trying to replace the Flame Amplifier Module.IMPORTANTTerminal Wiring BaseWhen wiring to the FLAME-MONITOR wiring base,scanner terminal S2 must be grounded when usingflame rod on photocell scanner. When using an infraredscanner (48PT2), ground S2 on all EB700’s labeled"ENG CODE 00". All other ENG CODE models do notrequire that S2 be grounded. Do not ground S2 whenusing ultra violet scanners.3page 3 - 1155