TM 5-3895-374-24-2
955-257
6.11 REFERENCE CALIBRATION
At this point in the calibration program the CONFIGURATION calibration has been completed. Three situations may exist.
a)
You have completed what you need to do and wish to return the controller to use. Push the PARAM key and
proceed to section 6.16.
b)
The controller will not advance when you push the PARAM key. Proceed with the following instructions. This
occurs usually when calibrating after a DATA LOST/PLEASE CAL.
c)
You wish to perform a REFERENCE calibration. Proceed with the following instructions.
CAUTION:
ENTRY INTO THE REFERENCE CALIBRATION ROUTINE WITHOUT PROPER CALIBRATION
EQUIPMENT MAY ERASE THE FACTORY CALIBRATION. DO NOT PROCEED WITH THESE
INSTRUCTIONS UNTIL YOU ARE PROPERLY PREPARED.
REFERENCE calibration refers to the procedure for calibrating the controller to an external input reference source. Before
starting a reference calibration you must be at one of these displays.
HI SPAN
OR
HI VAL
XXX
XXX
If you are not at one of these displays and wish to do a REFERENCE calibration push the PARAM DISPLAY key until "CAL
COMPLETE" appears. Then push the LAST key once.
A
security
code
protects
the
reference
calibration
procedures. To enter the reference calibration mode push
the two keys indicated in Figure 6-3 simultaneously.
CAUTION:
ALLOW AT LEAST A 20 MINUTE WARMUP
BEFORE ANY REFERENCE CALIBRATION
IS ATTEMPTED.
There are three stored calibration routines. The controller will automatically display the correct instructions for your
application.
6.12
Thermocouple Input calibration
6.13
RTD Input calibration
6.14
Process Input calibration
ECLIPSE INSTRUMENTATION DIVISION
(page 3 - 1121)
FIGURE 6-3