TM 5-3895-374-24-1GP470FAEXAMPLE2:Same as example 1 except Proportional Band - 80% (0.80)DEV=0.10" (same as example 1)0.10Output=0.80 x 1.0=0.125 Displayed as OUT 62.5 (50 + 12.5)(output decreases due to Pb increase)On Time=: 5 x 0.125 :=0.625 seconds (on time decreases)Relay1willbeonfor0.625secondsandofffor4.375seconds.EXAMPLE3:Same as example 1 except Cycle Time - 10 seconds.DEV=0.10" (same as example 1)Output=0.20 (same as example 1)On Time=: 10 x 0.20 :=2.0 seconds (on time increases due to cycle time increase)Relay1willbeonfor2secondsandofffor8seconds.EXAMPLE4:Same as example 1 except Dryer Draft - -0.15" wc.Since the measured draft is now less than the setpoint the deviation is a negative value and the controller will energizeRelay 2 in order to Open the exhaust damper. The on time of relay 2 is calculated as follows:DEV=(-0.20") - (-0.15")=-0.05"=-0.05"Output=0.50 x 1.0=-0.10 Displayed as OUT 40.0 (50 - 10)On Time=: 5 x -0.10 :=0.5 secondsRelay2willbeonfor0.5secondsandofffor4.5seconds.(page 3-50)