TM 5-3895-374-24-2
955-257
SYMPTOM
CAUSE
CORRECTION
Slow response to
Reset time is set too
Increase the resets
setpoint or load
short.
minute (R/M) and re-
change with
tuned check response by
controller
making a small setpoint
change.
Large overshoot on
Reset time is set too
Decrease the reset and
SP or load change
long.
recheck response by
making a small setpoint
change.
Stepwise response
Rate time is set too
Decrease rate time set-
to setpoint or load
long.
ting and recheck res-
changes.
ponse by making a small
setpoint change.
ECLIPSE INSTRUMENTATION DIVISION
(page 3 - 1130)