TM 5-3895-374-24-2955-2578.4 TROUBLESHOOTINGGUIDESYMPTOMCAUSECORRECTIONPower applied, dis-a) No power applied toa) Check power wiringplay does not light controller.and fusing.and controller doesb) Controller not en-b) Check if controllernot operate.gaged properly inis properly engagedhousing.in housing.No power to loada) Open connection toa) Check load wiringMeasurement indi-load.and load fuses.cates temperatureb) Check load connect-below setpoint.ions.Output indicator ison continuously.Erratic Controla) Cycle time is tooa) Reduce cycle time.long.When using electro-mechanical relay orcontactor, set cycletime at value justbelow point whereload cycling occurs.b) Proportional band isb) Increase PB adjust-too narrow.ment until load cyc-ling is eliminated.c) Rate time is tooc) Increase rate timeshort.adjustment.Controller operat-a) System dynamics re-a) Wait for system toing not at setpointquires more Time.reach setpoint.and calling forb) Improper sizing ofb) Larger source is100% power.source to load.required.Display shows InputThermocouple, RTD orCheck thermocoupleopen.input circuit open.and extension wirein circuits foropens.Inability to tunea) On controllers witha) In tuning procedurecontroller prop-dual 3-mode outputs,outlined previously,erly.resets and ratesfor the rate and resetboth outputs mustbe adjustments are setset to zerobefore to zero (turnedbeginning thetuning off).procedure.b) Cycle time is set toob) Reduce cycle time.long.ECLIPSE INSTRUMENTATION DIVISION(page 3 - 1129)