TM 5-3895-374-24-24.3 TUNINGFor actual tuning, proceed by pushing the PARAM DISPLAY key.At this display, you must decide if you want to tune the controller orTUNE ?return to the OPERATOR loop. Tuning is required on all initialOUTPUTSinstallations. If the NO key is pressed, the display goes to the "END OFTUNE" display. If the YES key is pressed, the following displays appearin sequence.DEAD BDIFor an ON/OFF primary output ONLY, select a DEADBAND of 0.25, 0.50, orX.XX%1.00% of Span using the arrow keys. Factory preset at 0.25% of Span.Push the PARAM DISPLAY key to advance.This display appears ONLY when the primary output is set for TimeCYCTIME1Proportional Control (TPR). Set a cycle time (CYCTIME) from 1 to 60XX SECseconds using the arrow keys-factory preset at 15 seconds. Push PARAMDISPLAY key to advance.The next display will vary depending on the controller model. Controllers without self tuning (Models 2000, 2001 and 2002)follow the manual tuning procedure in Section 4.5. Controllers with self tuning (Models 2003 and 2004) follow theprocedure in Section 4.4 below. All controllers with a secondary output must have the secondary output tuned manually.4.4 SELFTUNEPROGRAM(Models2003and2004only)SELF?6 This is the first display in the SELF TUNE program. Push the YES key forTUNE?SELF TUNE. Push the NO key if manual tuning of the primary output isdesired and proceed to Section 4.5.You must next choose the desired closed loop response of the system: FAST or SLOW. Different tuning rules areapplied by SELF TUNE according to your choice.FAST ?NOSLOW ?Indicate whether you want your system to be a FAST orRESPONSERESPONSESLOW responding system. Push the NO key to switchbetween these two displays. Push the YES key to selectYESYESthe desired response.Select FAST RESPONSE for systems where a possible overshoot will not present a hazard. Select SLOW RESPONSEwhere potential overshoot is not acceptable. Your decision can be changed at any later time without retuning by returningto these displays in the TUNE loop and selecting the other response.Push the NO key if you don’t want to start the SELF TUNE procedure. TheSTARTPID constants will then be calculated according to the last process modelTUNE ?and your choice of response. This allows you to change your choice ofFAST or SLOW tuning without repeating the self tuning program.Push the YES key to initiate the SELF TUNE program.SELFThe yellow TUN light will flash, and the display indicates that you areTUNINGin SELF TUNE mode. After a short delay (15 secs), Output 1 will turn ON,and the controller will start to analyze the system.ECLIPSE INSTRUMENTATION DIVISIONpage 3-1095
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business