TM 5-3895-374-24-2
FLAME AMPLIFIER SELECTION
Fireye P/N
Description
Use with Scanner
EUV1
Standard UV Amplifier
UV1A, UV8A,45UV3
EIR1
Autocheck Infrared Amplifier
48PT2
ERT1
Rectification Amplifier
45CM1, 69ND1
EUVS4
Self-Check UV Amplifier
4SUV5-1007/1008/1009
E1R3
Autocheck Infrared Amplifier
48PT2
(For use on solid fuel burners only)
SCANNER SELECTION
Fireye P/N
Description
Use with Amplifier
48PT2-1003
Infrared 1/2" straight mount 96" cable
48PT2-9003
Infrared 1/2" 900 angle mount 96" cable
E1R1
48PT2-1007
Infrared 1/2" straight mount 48" cable
48PT2-9007
Infrared 1/2" 900 angle mount 48" cable
UV1A3
UV 1/2" straight 36" flex conduit
UV1A6
UV 1/2" straight 72" flex conduit
UV8A
UV 1/2" 900 head 72" unshielded leads
EUV1
UV2
UV 3/8" straight 36" flex conduit
45UV3-1050
UV 3/4" cast alum. housing, 8 cable
45CM1-1000
Photocell Scanner with filter
45CM1-1000Y
Photocell Scanner without filter
69ND1-1000K4
Flame rod 12", 1/2" N.P.T. mount
ERT1
69ND1-1000K6
Flame rod 18", 1/2" N.P.T. mount
69ND1-1000K8
Flame rod 24", 1/2" N.P.T. mount
45UV5-1007
Self-check UV 1" British thread mounts, 230V
45UV5-1008
Self-check UV 1" British thread mounts, 120V
EUVS4
45UV5-1009
Self-check UV 1" N.P.T. threads, 120V
FLAME SCANNERS
CAUTION: The UV1, UV2, UV8, and 45UV3 ultra-violet name scanners and associated
amplifier modules are non-self-checking UV systems and should be applied only to burn-
ers that cycle often (e.g. a minimum of once per 12 hours) in order for the safety checking
circuit to be exercised. (see Operation). If component checking is required during burner
operation for constantly fired burners, utilize the self-checking ultra-violet flame scan-
ners (45UV5) and associated amplifier module (EUVS4).
FLAME SAFEGUARD
(page 3 - 1042)