DESCRIPTION
The FIREYE® FLAME-MONITORTM System is a microprocessor based, burner management control
system with self-diagnostics, non-volatile memory and vocabulary of 42 different messages which
scroll out on the message center to provide the operator with status and failure mode information.
The FLAME-MONITOR Series is designed to provide the proper burner sequencing, ignition and
flame monitoring protection on automatically ignited oil, gas and combination fuel burners. In
conjunction with limit and operating controls, it programs the burner/blower motor, ignition and fuel
valves to provide for proper and safe burner operation. On a safety shutdown, the message center will
advise the operator that the control is in "lockout' and scroll a message indicating the cause as well
as the position in the sequence it occurred.
Interchangeable programmer and flame amplifier modules allow for complete versatility in selection
of control function, timing and flame scanning means. Functions such as pre-purge timing, recycling
interlocks, high fire proving interlock and trial for ignition timing of the pilot and main flame are
determined by the programmer module. The FLAME-MONITOR can be used with ultraviolet,
autocheck infrared, photocell, flame rod or self-check ultraviolet flame scanners by choosing the
proper amplifier module.
The eighteen terminal wiring base allows for many functional circuits including motors, valves and
ignition transformers as well as multiple interlocks such as hi-purge, low purge, fuel valve and running
circuits. The FLAME-MONITOR uses the same wiring base as the Fireye D Series and C Series
Controls -..d is designed to be directly interchangeable with most models without rewiring.
(page 3- 1037)