TM 5-3895-374-24-1
GP44UFG
3.
Constant gas pressures ranging from 10 psig minimum to 25 psig maximum must be available at the inlet of the
Hauck gas pilot manifold.
4.
Complete the initial adjustment of the air shutter in the following manner:
a.
Loosen, but do not remove, the locking thumbscrew.
b.
Adjust the air shutter to approximately ¼ opening.
c.
Securely tighten the locking thumbscrew.
d.
Open the gas flow valve slowly and light the pilot by means of electric ignition.
Fig. 6-StarJet AIG Pilot System
Fig. 7-Pilot Scanner, Adapter
(page 3-507)