TM 5-3895-374-24-1
GENERAL INFORMATION
While these instructions are intended as a general
recommended guide, they do not supersede any national
and local codes in any way Authorities having jurisdiction
should be consulted before the installation is made
These instructions and any instructions packaged with
separate equipment, required to make up the entire air
conditioning system, should be carefully read before
beginning the installation Note particularly "Starting
Procedure" and any tags and labels attached to the
equipment
These instructions explain the recommended methods
for installing the unit and for making the electrical wiring
connections to the unit All internal wiring is complete The
refrigerant system Is completely assembled and charged
Service ports have been provided for field charging when
needed
Sizing of units for a proposed installation should be
based on heat-gain and loss calculations made
according to the methods of the National Warm Air
Heating and Air Conditioning Association The air duct
should be Installed In accordance with the Standards of
the National Fire Protection Association for the
Installation of Air Conditioning and Ventilating Systems of
Other Than Residence Type, NFPA No 90A, and
Residence Type Warm Air Heating and Air Conditioning
Systems, NFPA No 90B Where local regulations are at a
variance with these instructions, Installer should adhere
to local codes
All capacity and efficiency Information is based on units
operated without a fresh air intake kit installed
UNPACKING THE UNIT
It Is recommended that the unit be unpacked at the
installation site to minimize damage due to handling
CAUTION
Do not tip the unit on its side. Oil may enter the
compressor cylinders and cause starting or operating
problems.
1 Cut and remove bands from around unit
2 Remove the carton from the unit
3 Inspect unit for any shipping damage In case of
damage,
notify carrier immediately of damage claim
4 Remove unit mounting hardware attached to sides of
unit
5 If unit has been set on its side, restore it to Its upright
position and do not run for several hours Then run unit
for a few seconds only Repeat this three or four times at
intervals of ten minutes
LOCATING THE UNIT
The decision on where to locate the equipment should
be based on keeping the length of the supply and return
air ducts to a minimum consideration should also be
given to shade, noise, appearance and sufficient
clearance for air flow through inlet and outlet Allow a
minimum of 12" below unit and 18" on each side of unit
for air flow
CONDENSATE DRAIN
Provide an appropriate drain system A plastic drain tube
extends from the drain pan down through the unit base
pan If a drain hose is connected to a drain system It
must be an open or vented system to assure proper
drainage
DUCTWORK
This unit Is designed for use WITH or WITHOUT
Flanges are provided for attaching supply and return air
ducts (Refer to Page 7, for examples of some typical
installations with and without ductwork) Some
Installations may not require a return air duct It Is
recommended that on this type of installation that a filter
grille be located in the wall Filters must be of sufficient
size to allow a maximum of 400 FPM (Applicable
Installation codes may limit an unducted return
air installation to a single story residence only)
Design the ductwork according to methods given by the
National Warm Air Heating and Air Conditioning
Association (ACCA) The ACCA Manuals provide an
excellent guide to proper sizing.
When a duct runs through unheated spaces, It must be
well insulated to prevent heat loss and condensation Use
insulation with a vapor barrier on the outside of the
insulation.
A one inch clearance to combustible material on all four
sides of the supply air duct Is required for the first
THREE FEET of duct attached to the outlet air frame for
all PWY units
AIR FILTER
A one inch throwaway air filter is supplied with the unit
The filter slides In and out making It easy to service Filter
is serviced from the outside by removing the service
panel
RATED CFM AND E S P (WET COIL COOLING)
Unit Size
-018
024
030
036
042-
048
-060
Ratedcf
m
720
810
112
5
1250
157
5
1700
1750
Ext sp
32
20
30
20
35
25
20
CFM AND EXTERNAL STATIC PRESSURE WET COIL
PERFORMANCE
Ext. s.p.
Unit Size
-018/-024
-030/-036
042/-0481-060
10
860
1365
-
15
850
1310
-
20
810
1250
1750
25
780
1210
1700
30
750
1125
1650
35
690
1075
1575
40
670
-
1510
50
-
-
048
OPTIONAL FRESH AIR INTAKE KIT
A Fresh Air Intake Kit Is available as "optional
equipment" The kit Includes an adjustable damper and
may be field Installed to the service panel as shown on
Page 4 NOTE Some state and local codes require fresh
air capability
(page 3-485)