TM 5-3895-374-24-1
Connections
Equipment required
ATV-452075 (N) to D30 (N) 380/415V
(N 440/500 V)
M1
Motor (kW/ HP)
0,75/1
1,5/2
2,2/3
3/4
4/5,5
5,5/7,5
7,5/10
11/15
15/20
18,5/25
22/30
30/40
A1
ALTIVAR ATV-
452
075(N)
U15(N)
U22(N
)
U30
U40(N)
U55(N)
U75(N
)
D11(N)
D15(N)
D18N
D22(N)
D30(N)
Q1
Isolator
LS1-D2531 A65
GK1-
EK
DK1 -FB
DK1-
GB
+ 3 fuses type
gl DF2-
CN04
CN06
CN10
CN12
CN16
CN20
CN25
EN40
FN50
FN63
FN80
FN100
KM
1
Contactor LC1-
D
0910
0910
0910
0910
1210
1810
2510
3210
4011
5011
6511
8011
Suppressor
LA4-DA2U
T1
Transformer
63 VA
100 VA
160 VA
ATV-452D37 (N) to D90 (N) 380/415 V (N 440/500 V)
M1
Motor (kW / HP)
37/50
55/75
75/100
90/125
A1
ALTIVAR ATV-452
D37(N)
D55 (N)
075 (N)
D90 (N)
Q1
Isolator
DK1-HC
DK1-HC
DK1-JC
DK1-JC
+ 3 fuses type gl
DF2-GN1121
DF2-GN1161
DF2-HN1201
DF2-HN1251
KMl
Contactor
LC1-D8011--
LC1-F115
LC1-F150
LC1-F185
+ coil
LX1-FF
LX1-FF
LX1-FG
Suppressor
LA4-DA2U
LA9-F980
LA9-F980
LA9-F980
T1
Transformer
160 VA
250 VA
250 VA
400 VA
Equipment required, all ratings, all models
F1
Fuse type aM
DF2-CA02
F2
Fuse type gl*
Fuse carriers
DF2-CN02, DF2-CN04 for D55 (N), D75 (N) and D90 (N) (If 220 V control)
DF6-AB10
R
Potentiometer
SZ1-RV1202
S1-S2
Push-buttons
XB2-B
* or GB2-C circuit breaker
Cabling
Terminals
For ALTIVAR
Recommended section
mm2
AWG
CL1-CL2--PL-FW-RV-DCB-SA-SB
All ratinqs
1
18
OE1-E1-P10-E2-EC
All ratings
1 (twisted cable)
18
L1-L2-L3-U/T1-V/T2-WIT3
ATV-452075 (N), U15 (N)
1,5
16
ATV-452U22 (N), U30
2,5
14
ATV-452U40 (N), U55 (N)
2,5
14
ATV-452U75 (N)
4
12
ATV-452D11 (N), D15(N)
6
10
ATV-452D18N, D22 (N)
10
8
ATV-452D30 (N)
16
6
ATV-452D37 (N)
25
4
ATV-452D55 (N)
35
1
ATV-452D75 (N)
50
00
ATV-452D90 (N)
70
000
PA-PB ATV-452D37 (N), 055 (N)25
4
ATV-452D75 (N), D90 (N)
2 x 25 n //
2 x 4
(page 3-173)