TM 5-3895-374-24-1FIGURE 4CONNECTIONSConnections for standard application should be made according to the wiring diagram In Figure 2 Wires from the Sensorto the Ground Fault Relay should be no longer than 25 feet and no smaller than No. 14 AWG. Wires from MonitorComponents should be no longer than 50 feet and no smaller than No 18 AWG Wires 1, 2 and 3 and Control Transformershould be sized to deliver the necessary current to the Trip Coil at 55% rated output voltage of the Control Transformer.When zone selective interlock wiring Is used, Ground Fault Relay interconnections should be no smaller than No. 18 andno longer than 100 feet These wires should be routed separately from any power wiringAll wiring should be protected from arcing fault and physical damage by barriers, conduit, armor or location.When two wires are used under one terminal on the Sensor, both shall be No. 14.(page 3-92)
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business