Identifying 5/02 Processor Communication Errors - TM-5-3895-374-24-1_470
Clearing 5/03 Processor Faults Using the Keyswitch

TM-5-3895-374-24-1 Paving Machine Bituminous Material: Crawler Mounted Diesel Engine Driven Manual
Page Navigation
  425    426    427    428    429  430  431    432    433    434    435  
TM 5-3895-374-24-1 Chapter 9 Troubleshooting The Following Probable Cause Recommended Action Error Exists 1.  Check communication parameters of programmer Programmer and processor baud rate must match The 5/02 Programmer and processor node addresses must be processor is DH-485 different receiving data, communication but is not parameters are 2.  Try different combinations of communicating parameters are a.  baud rate (Processor default is 19200) with the improperly set up b.  node address (Processor default is 1 ) programmer 3.  Try to increase the maximum node address (Default is 31 ) Refer to the following key to determine the status of the LED indicators Indicates the LED is OFF Indicates the LED is ON Indicates the LED is FLASHING Status of LED does not matter The RUN LED on the 5/01 processor is actually labeled "PC RUN " Also, the 5/01 processor does not have a COMM LED (page 3-443)