TM 5-3895-374-24-2EP160 ADDITIONAL MESSAGESHOLD MESSAGESDESCRIPTIONThe running interlock circuit (3-P) has opened during the burner onperiod. This message will be on the display for 15 sec. (post purge)and then the appropriate lockout message will appear.The running interlock circuit (3-P) has opened during the main trialfor ignition period. This message will be on the display for 15 sec.(post purge) and then the appropriate lockout message will appear.The running interlock circuit (3-P) has opened during the pilot trialfor ignition period. This message will be on the display for 15 sec.(post purge) and then the appropriate lockout message will appear.The control has driven the firing rate motor to high purge and is wait-ing for the high fire switch (D-8) to close. It will hold in this positionfor ten minutes and then lockout if the D-8 circuit does not close.The flame has been sensed sometime during the burner off time. Thismessage will hold for 60 seconds and display Flame Signal (00)strength. This can be used as an aid in trouble shooting scanners andamplifiers.A flame failure occurred during the main burner on period. The con-trol will hold this message for 15 sec. (post purge) and then lockoutNo flame was proven during the main trial for ignition period. Thecontrol will hold this message for 15 sec. (post purge) and then lock-outNo flame was proven during the pilot trial for ignition period. Thecontrol will hold this message for 15 sec. (post purge) and then lock-outSee description on page 15 for "LOCKOUT CHECK SCANNER"The control has finished purge and the firing rate motor is driving tothe low fire position waiting for that switch (M-D) to close. It willhold in this position for ten minutes and then lockout if the M-D cir-cuit does not close.See description on page 14 for "LOCKOUT SCANNER NOISE"The control has sensed an excessive current or short circuit externalto Terminals 5, 6, or 7. This message will hold for 15 sec. (post purge)and then the control will lockout on the second consecutive event anddisplay the appropriate message.Note:Messages more than 8 characters in length will scroll continuously from right to left on the display.FLAME SAFEGUARD(page 3 - 1048)
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business