TM 5-3895-374-24-1
GP470FA
4.
Press [SET UP] again until the display reads SET UP INPUT2.
5.
Press the [FUNCTION] key once. The lower display will read IN2 HI.
6.
Use the
] or
] keys to change the upper display to the setpoint value desired when the burner is firing at
100% (this would be -0.30 for the example given above).
7.
Press [FUNCTION] again then use the
] or
] keys to change the upper display to the setpoint value desired
when the burner is at low fire (-0.05 for the above example).
8.
Press the [SET UP] key again. The controller display will read SET CONTRL.
9.
Press the [FUNCTION] key until the lower display reads SP SRC then use the
key to change the upper display
to REM.
10.
Press the [DISPLAY] to exit the set up mode and return to normal operation.
An "L" appearing at the lower right of the controller display indicates that the controller is using its local setpoint for control.
Pressing the FUNCTION key will change "L" to "R" and the controller will use the remote setpoint generated by the signal
converter module.
(page 3-45)