TM 5-3895-374-24-1GP467FB9.Set the internal FUEL SELECTOR switch to the desired fuel position10. Adjust the remaining limit switches to the values required by your application. Consult the Manufacturer’s literature forthe proper method of switch adjustment.11. Final adjustment of the low and high pressure switches should be made at the time of Initial startup. To adjust theLOW air pressure switch, reduce the air pressure at the burner until the burner goes out or Improper combustion takesplace * The pressure should then be increased by whatever amount is necessary to maintain ignition or the desirablecondition.* The LOW fuel pressure switches should also be adjusted to break at a pressure just below that required tomaintain burner ignition at the desirable condition.* The HIGH fuel pressure switches should be adjusted to break at apressure just above that obtained at the burner during correct high fire operation. Refer to vendor literature for correctmethod of switch adjustment.*IMPORTANTFuel flows should not exceed the amount of available air for combustion In normal operation in order toprevent formation of carbon monoxide and/or unburned fuel. The fuel flows should be limited by settingthe high fuel pressure switches to prevent incomplete combustion in normal circumstances If atmosphereis of a reducing type (i.e. , CO or unburned fuel present), additional safety precautions will dictate theproper setting of the high pressure switches.E.FINALCHECKOUT1.Be sure that all equipment and components have been installed in accordance with the manufacturer’s Instructionsand drawings.2.Verify that all necessary preliminary adjustments have been made.3.Be sure all switches and valves are properly installed and correctly wired4.Be sure all traps and filters in the system which may have accumulated dirt or other foreign material5.Make a final check of all fuel and air supply lines for leaks caused by loose fittings, unions, valves, etc.F.PANELOPERATION1.With the panel power OFF, open the hinged door and verify that the FUEL SELECTOR switch is In the desiredposition.2.Open all manual shutoff valves to supply air and fuel to the system.3.Place the panel POWER switch in the ON position, the following events will occur.a. The alarm horn will sound. Press the ALARM SILENCE pushbutton.b. The burner control motor will drive to Its low fire position.c. The Tertiary Air Damper, If applicable, will drive OPEN for purge.(page 3-14)
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business